Problem 9.7

 

Given

 

Application single-story commercial building
Panel 15/32-in. thick 32/16 span-rated STRUCTURAL I sheathing
Edge Support unblocked
Nails 8d common
Critical lateral forces wu = wT = 320 lb/ft  (strength level seismic, transverse direction)
wu = wL = 570 lb/ft  (strength level seismic, longitudinal direction)

Figure 9.A

 

 

a. Adjusted chord forces: maximum and at each end of wall openings

 

Transverse Loading

Middle of 80-ft wall

Maximum moment:  Mu = wTL2/8 = 320 lb/ft (80 ft)2 / 8 = 256,000 lb-ft  (see moment diagram above)

Maximum LRFD tension & compression:  Tu = Cu = Mu/b = 256,000 lb-ft / 35 ft = 7,314 lb

Maximum ASD tension & compression:  T = C = 0.7Tu5,120 lb

 

West end of header in 80-ft wall

Vmax = R = wT (80 ft) / 2 = (320 lb/ft)(80 ft) / 2 = 12,800 lb

By similar triangles on V diagram, 

Vmax / 40 ft = Vwest / 25 ft

Vwest = 8,000 lb

Mwest = Mu = area under first portion of the V diagram = 15 ft x Vwest + 0.5 x 15 ft x (Vmax - Vwest) = 156,000 lb-ft

Tu = Cu = Mu/b = 156,000 lb-ft / 35 ft = 4,457 lb

T = C = 0.7Tu3,120 lb

 

East end of header in 80-ft wall

Vmax = R = wT (80 ft) / 2 = (320 lb/ft)(80 ft) / 2 = 12,800 lb

By similar triangles on V diagram, 

Vmax / 40 ft = Veast / 20 ft

Veast = 6,400 lb

Meast = Mu = area under last portion of the V diagram = 20 ft x Veast + 0.5 x 20 ft x (Vmax - Veast) = 192,000 lb-ft

Tu = Cu = Mu/b = 192,000 lb-ft / 35 ft = 5,486 lb

T = C = 0.7Tu3,840 lb

 

 

Longitudinal Loading

 

Middle of 35-ft wall

Maximum moment:  Mu = wLb2/8 = 570 lb/ft (35 ft)2 / 8 = 87,280 lb-ft  (see moment diagram above)

Maximum LRFD tension & compression:  Tu = Cu = Mu/L = 87,280 lb-ft / 80 ft = 1,091 lb

Maximum ASD tension & compression:  T = C = 0.7Tu763.7 lb

 

North end of header in 35-ft wall

Vmax = R = wL (35 ft) / 2 = (570 lb/ft)(35 ft) / 2 = 9,975 lb

By similar triangles on V diagram, 

Vmax / 17.5 ft = Vnorth / 2.5 ft

Vnorth = 1,425 lb

Mnorth = Mu = area under last portion of the V diagram = 15 ft x Vnorth + 0.5 x 15 ft x (Vmax - Vnorth) = 85,500 lb-ft

Tu = Cu = Mu/b = 85,500 lb-ft / 80 ft = 1,069 lb

T = C = 0.7Tu748.1 lb

 

South end of header in 35-ft wall

Msouth = Mu = 0

Tu = Cu = Mu/b = 0

T = C = 0.7Tu0

 

 

b. Plot strut forces for walls with openings

 

Transverse Loading

Vmax = R = wT (80 ft) / 2 = (320 lb/ft)(80 ft) / 2 = 12,800 lb

vroof = R/b = 12,800 lb / 35 ft = 365.7 lb/ft
v
wall = R/b = 12,800 lb / 15 ft = 853.3 lb/ft

 

North end of header in 35-ft wall

Tu = Cu = (15 ft) |vwall - vroof| = (15 ft) | 853.3 lb/ft - 365.7 lb/ft | = 7,314 lb

T = C = 0.7Tu5,120 lb

 

Middle of 35-ft wall

Tu = Cu = (15 ft) |vwall - vroof| - 2.5 ft (vroof) = (15 ft) | 853.3 lb/ft - 365.7 lb/ft | - 2.5 ft (365.7 lb/ft) = 6,400 lb

T = C = 0.7Tu4,480 lb

 

South end of header in 35-ft wall

Tu = Cu = 0

T = C = 0.7Tu0

 

 

Longitudinal Loading

Vmax = R = wL (35 ft) / 2 = (570 lb/ft)(35 ft) / 2 = 9,975 lb

vroof = V/b = 9,975 lb / 80 ft = 124.7 lb/ft
v
wall = V/b = 9,975 lb / 35 ft = 285.0 lb/ft

 

West end of header in 80-ft wall

Tu = Cu = (15 ft) |vroof - vwall| = (15 ft) | 124.7 lb/ft - 285.0 lb/ft | = 2,405 lb

T = C = 0.7Tu1,684 lb

 

Middle of 80-ft wall

Tu = Cu = | (40 ft) (vroof) - 15 ft (vwall) | = | (40 ft) (124.7 lb/ft) - 15 ft (285.0) | = 713 lb

T = C = 0.7Tu499.1 lb

 

East end of header in 80-ft wall

Tu = Cu = (20 ft) |vroof - vwall| = (20 ft) | 285.0 lb/ft - 124.7 lb/ft | = 3,206 lb

T = C = 0.7Tu2,244 lb

 

 

b. Compare chord and strut forces

 

LRFD values

Location Transverse Loading Longitudinal Loading
Chord force (lb) Strut force (lb) Chord force (lb) Strut force (lb)
80-ft
wall
west end of header 4,457     2,405
middle of wall 7,314     713
east end of header 5,486     3,206
35-ft
wall
north end of header   7,314 1,069  
middle of wall   6,400 1,091  
south end of header   0 0  

∴ Chord force > strut force at a particular point for transverse loading; Chord force < strut force at a particular point for longitudinal loading

Maximum load = 7,314 lb

 

ASD values

Location Transverse Loading Longitudinal Loading
Chord force (lb) Strut force (lb) Chord force (lb) Strut force (lb)
80-ft
wall
west end of header 3,120     1,684
middle of wall 5,120     499
east end of header 3,840     2,244
35-ft
wall
north end of header   5,120 748  
middle of wall   4,480 764  
south end of header   0 0  

Maximum load = 5,120 lb