Sample House

 

FOUNDATION LEVEL

 

Side Stem Wall  (loaded by roof)

 

End Stem Wall  (not loaded by roof)

 

Side Sill Plate (loaded by roof)

 

End Sill Plate  (not loaded by roof)

 

Floor Beam

 

Sorted by Load Source Sorted by Component

Floor Beam

  • dead load
    • wD = 10.99 lb/ft
  • deflection limits
    • 0.2000 in.  for L
    • 0.3000 in. for D + L  (or L + 0.5D if under dry conditions)
need to go back and calculate distributed loads instead of point loads...and consider using load reductions due to larger AT

Stem Wall Under Side Wall

  • loads
    • PD = 108.9 lb (from rafter) + 110.1 lb (from second-floor ceiling joist) + 86.40 lb (from second-floor exterior side wall) + 86.4 lb (from first-floor exterior side wall) + 104.5 lb (from second-floor floor/ceiling joist) + 2.748 lb/ft (16 in. x 1 ft/12 in.) (from second-floor rim joist) + 81.20 lb (from first-floor floor joist) + 2.748 lb/ft (16 in. x 1 ft/12 in.) (from first-floor rim joist)
    • PLr = 220.0 lb (from rafter)
    • PL = 110.0 lb (from second-floor ceiling joist) + 440.0 lb (from second-floor floor/ceiling joist) + 440.0 lb (from first-floor floor joist)
    • PS = 396.0 lb (from rafter)

Stem Wall Under End Wall

  • loads
    • PD = 86.40 lb (from second-floor exterior end wall) + 86.40 lb (from second-floor exterior side wall) + 2.748 lb/ft (16 in. x 1 ft/12 in.) (from second-floor rim joist) + 162.4 lb (from first-floor floor joist) + 2.748 lb/ft (16 in. x 1 ft/12 in.) (from first-floor rim joist)

Floor Beam

  • loads
    • loads
      • PD = 184.8 lb (from rafter) + 5.422 lb (from pony wall) + 220.3 lb (from ceiling joist) + 61.89 lb (from second-floor interior wall) + 209.1 lb (from second-floor floor/ceiling) + 61.89 lb (from first-floor interior wall) + wD = 10.99 lb/ft (for its own mass)
      • PLr = 373.4 lb (from rafter)
      • PL = 186.7 lb (from ceiling joist) + 746.8 lb (from second-floor floor/ceiling joist) + 746.8 lb (from first-floor floor joist)
      • PS = 336.1 lb (from rafter)