Sample House
ROOF LEVEL
Roof
- dimensions
- building footprint: 48' x 28'
- roof pitch: 4:12
- eave overhang: 24" (actually about 1.25 ft in AutoCAD drawing)
- rafter rise and run: 61 in. vertical, 15.25 ft horizontal (AutoCAD drawing)
- dead load
- pressure
- shingles: 30 lb. felt and asphalt shingles = 2.2 psf x 3 layers of shingles = 6.2 psf
- sheathing: 1/2" plywood = 3.0 x 1/2 = 1.5 psf
- rafter: 2x8 at 16" OC = 1.6123 psf
- D = 9.4 psf (angled) = sqrt (42 + 122)/12 x 9.4 = 9.9 psf (horizontal)
- load to rafter
- wD = 9.9 psf x 16 in. (1 ft/12 in.) = 13.20 lb/ft
- load to stud in pony wall
- AT = 16 in. (1 ft/12 in.) x (7 ft) x 2 sides = 18.67 ft2
- PD = D AT = 184.8 lb
- load to stud in exterior side wall
- AT = 16 in. (1 ft/12 in.) x (8.25 ft) = 11.00 ft2
- PD = D AT = 108.9 lb
- live load
- pressure
- L0 = 20 psf (horizontal, ASCE 7 table 4-1)
- load to rafter
- AT = 16 in. (1 ft/12 in.) x (15.25 ft) = 20.33 ft2
- R1 = 1 (ASCE 7 section 4.9.1)
- R2 = 1 (F ≤ 4)
- Lr = 1 * 1 * 20 psf = 20 psf
- wLr = 20 psf x 16 in. (1 ft/12 in.) = 26.67 lb/ft
- load to stud in pony wall
- AT = 16 in. (1 ft/12 in.) x (7 ft) x 2 sides = 18.67 ft2
- R1 = 1 (ASCE 7 section 4.9.1)
- R2 = 1 (F ≤ 4)
- Lr = 1 * 1 * 20 psf = 20 psf
- PLr = Lr AT = 373.4 lb
- load to stud in exterior side wall
- AT = 16 in. (1 ft/12 in.) x (8.25 ft) = 11.00 ft2
- R1 = 1 (ASCE 7 section 4.9.1)
- R2 = 1 (F ≤ 4)
- Lr = 1 * 1 * 20 psf = 20 psf
- PLr = Lr AT = 220.0 lb
- snow load (ASCE 7 section 7.4)
- pressure
- Pg= 20 psf
- Cs = 1 (not slippery)
- Ce = 0.9 (fully exposed)
- Ct = 1 (heated)
- I = 1 (residential)
- S = 0.7 Cs Ce Ct I pg = 18.00 psf
- load to rafter
- wS = 18.00 psf x 16 in. (1 ft/12 in.) = 24.00 lb/ft
- load to stud in pony wall
- AT = 16 in. (1 ft/12 in.) x (7 ft) x 2 sides = 18.67 ft2
- PS = D AT = 336.1 lb
- load to stud in exterior side wall
- AT = 16 in. (1 ft/12 in.) x (8.25 ft) x 2 sides = 22.00 ft2 (that looks like a mistake; it should probably be 1 side)
- PS = D AT = 396.0 lb
- wind load
- ignore
- seismic load
- ignore
- deflection limits (IBC table 1604.3)
- not supporting ceiling
- L/180 for L = 14 ft x 12in./ft / 180 = 0.9333 in.
- L/180 for S or W = 0.9333 in.
- L/120 for D + L (or L + 0.5D if under dry conditions) = 1.400 in.